Statement 1071Warning Definition
IMPORTANT SAFETY INSTRUCTIONS
Before you work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar
with standard practices for preventing accidents. Read the installation instructions before using, installing, or
connecting the system to the power source. Use the statement number at the beginning of each warning
statement to locate its translation in the translated safety warnings for this device.
SAVE THESE INSTRUCTIONS
Warning
Statement 1074Comply with Local and National Electrical Codes
To reduce risk of electric shock or fire, installation of the equipment must comply with local and national
electrical codes.
Warning
Statement 1017Restricted Area
This unit is intended for installation in restricted access areas. Only skilled, instructed, or qualified personnel
can access a restricted access area.
Warning
Rack Requirements
Rack Specification
The rack must be of the following type:
Rack Type: A standard 19-inch (48.3 cm) wide, four-post EIA rack.
Mounting Posts: Must conform to universal hole spacing as per ANSI/EIA-310-D-1992.
Rack-Post Holes:
Square: 9.5 mm
Round: 7.1 mm
Vertical Rack Space: Minimum vertical rack space per server is 2 rack units (2U), equal to 3.5 inches
(88.9 mm).
Cisco UCS C885A M8 Server Installation and Service Guide
33