Product Manual — Doc. 9349B Crestron Zūm® Wired Solutions • 59
TEST (1) Pushbutton and (1) green LED, press and release the button to toggle the
load output on and off, press and hold to cycle the dimming level up and down,
LED indicates the load output is energized, also used for room setup and
factory reset
DIMMODE (1) Pushbutton (behind cover), press to cycle through dimming modes: auto
detect (default), reverse phase, forward phase, or center phase
AUTO (1) Red LED, indicates auto load type detection is selected and enabled
REV (1) Red LED, indicates reverse phase mode is enabled (automatically or
manually)
FWD (1) Red LED, indicates forward phase mode is enabled (automatically or
manually)
CENTER (1) Red LED, indicates center phase mode is enabled (manually)
ZEROCROSS FILTER (1) Pushbutton (behind cover), press to select zero-cross detection mode
BASIC (1) Green LED (behind cover), indicates when using basic zero-cross detection
FILTER (1) Green LED (behind cover), indicates when using filtered zero-cross detection
(default)
RESET (1) Pushbutton (behind cover), initiates hardware reset
LINK (1) bi-color green/red LED;
LED lights green in normal operation;
LED lights red when a fault is detected
ERROR (1) Red LED, indicates a variety of error conditions via blinking patterns
PWR Status (1) Green LED (behind cover), indicates line power is applied to either LINE
terminal
Connections
ZUMLINK (2) RJ-45 orange ports;
In-room Zūm Link device daisy-chaining
NEUT (3) Captive screw terminals;
Neutral connections for feed and load;
24 to 10AWG (0.25 to 4.0mm2) wire size
LINE (2) Captive screw terminals;
Line power feed input and pass-through;
24 to 10AWG (0.25 to 4.0mm2) wire size
LOAD (1) Captive screw terminal;
Dimmed load output;
24 to 10AWG (0.25 to 4.0mm2) wire size
Ground (1) 3-terminal grounding block
Environmental
Temperature 32° to 104°F (0° to 40°C)
Humidity 10% to 90% RH (noncondensing)
Construction