96 Crestron Zūm® Wired Solutions Product Manual Doc. 9349B
Load Controller Installation
The Zūm Net and Zūm Link junction box load controllers mount directly to a 4 in. square junction
box (not included) and connects to other Zūm devices via CBL-CAT5E-ZUMLINK-P or
CBL-CAT5E-ZUMNET-P cables (sold separately, refer to Cables on page 14). For installing the
universal dimmer load controller, refer to Universal Dimmer Load Controller Installation on page
105.
NOTES:
l
Zūm Net load controllers facilitate communications between rooms via
CBL-CAT5E-ZUMNET-P cables (sold separately) and can be daisy-chained for
network expansion. Zūm Link devices connect to ZUMNET-JBOX devices to provide
in-room lighting control
l
Zūm Link load controllers allow for in-room lighting control through compatible
keypads and sensors. Two RJ-45 ports on the device and the CBL-CAT5E-ZUMLINK-P
cables (sold separately) allow for connection to a Zūm Net device and for in-room
device daisy-chaining.
In the Box
Qty. Description
1 ZUMNET-JBOX-16A-LV, ZUMNET-JBOX-DALI, ZUMLINK-JBOX-16A-LV,
ZUMLINK-JBOX-20A-PLUG, or ZUMLINK-JBOX-20A-SW Wired J-Box Load Controller
Additional Items
5 Yellow Wire Nut, 22-10 AWG (2049245)
1 Locknut (2047626)
1 Tie Wrap (2005429)