EasyManua.ls Logo

Danfoss iC2-Micro Series - Automatic Derating

Danfoss iC2-Micro Series
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
120
100
80
60
40
20
0
0
2
4 6 8 10 12 14 16 18
e30bv166.10
I
out
(%)
f
switch
(kHz)
40 °C (104 °F)
50 °C (122 °F)
55 °C (131 °F)
Figure 24: Derating of Output Current Versus Switching Frequency (MA03a 3x380–480VAC)
120
100
80
60
40
20
0
0
2
4 6 8 10 12 14 16 18
e30bv167.10
I
out
(%)
f
switch
(kHz)
40 °C (104 °F)
50 °C (122 °F)
55 °C (131 °F)
Figure 25: Derating of Output Current Versus Switching Frequency (MA04a 3x380–480VAC)
120
100
80
60
40
20
0
0
2
4
6
8 10 12 14 16 18
e30bl439.10
I
out
(%)
f
switch
(kHz)
40 °C (104 °F)
50 °C (122 °F)
55 °C (131 °F)
Figure 26: Derating of Output Current Versus Switching Frequency (MA05a 3x380–480VAC)
4.9.3 Automatic Derating
To ensure the performance at critical stages, the drive checks for the following critical levels constantly and adjusts the switching
frequency automatically.
l Critical high temperature on the heat sink.
l High motor load.
l Low motor speed.
l Protection signals (overvoltage/undervoltage, overcurrent, ground fault, and short circuit) are triggered.
56 | Danfoss A/S © 2024.08 AJ402315027937en-000401 / 130R1239
Design Guide | iC2-Micro Frequency Converters Specifications

Table of Contents