EasyManua.ls Logo

Danfoss iC2-Micro Series - Page 95

Danfoss iC2-Micro Series
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Design Guide | iC2-Micro Frequency Converters Electrical Installation Considerations
e30bv091.10
Figure 51: Correct Connection of the Cable Shield
The preferred method is to secure control and serial communication cables with shielding clamps provided at both ends to ensure the
best possible high-frequency cable contact.
If the ground potential between the drive and the PLC is different, electric noise could disturb the entire system. Solve this problem by
fitting an equalizing cable as close as possible to the control cable. Minimum cable cross-section: 16 mm
2
(6 AWG).
1
2
PE
FC
PE
PLC
e30bb922.12
PE
PE
<10 mm
Figure 52: Shielding Clamps at Both Ends
1
Minimum 16 mm
2
(6 AWG)
2 Equalizing cable
With long control cables, ground loops may occur. To eliminate ground loops, connect the end of the shield to the ground with a 100nF
capacitor (keeping leads short).
100nF
FC
PE
PE
PLC
<10 mm
e30bb609.12
Figure 53: Connection with a 100 nF Capacitor
To avoid EMC noise on serial communication, terminal 61 is connected to ground via an internal RC link. Use twisted-pair cables to
reduce interference between conductors. The recommended method is shown in Figure 54.
Danfoss A/S © 2024.08 AJ402315027937en-000401 / 130R1239 | 95

Table of Contents

Related product manuals