8 Settings
Installation and Operation Manual for RPI M50A
82
Installation and Operation Manual for RPI M50A
82
Congurable Parameters
Parameter Description
Mode OFF Switches the function on and off.
Curve A
Curve B
V1s
The lower voltage limit for feeding-in capacitive reactive power.
V2s
The upper voltage limit for feeding-in capacitive reactive power.
Qs limit
The limit for the inductive apparent power. The value is set in per cent of the rated
apparent power S
n
. This value is with parameter V2s.
V1i
The upper voltage limit for feeding-in inductive reactive power.
V2i
The upper voltage limit for feeding-in inductive reactive power.
Qi limit
The limit for the inductive apparent power. The value is set in per cent of the rated
apparent power S
n
. This value is with parameter V2s.
T delay
Internal parameter
P lock-in
The lower limit of the active power range within which the function is active. The
parameter is given in percent of the nominal power. Used for Italy only.
P lock-out
The upper limit of the active power range within which the function is active. The
parameter is given in percent of the nominal power. Used for Italy only.
Do not change this setting without prior
consultation with Delta Solar Support.