EasyManua.ls Logo

DencoHappel MATRIX OP71 - Page 64

Default Icon
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating MATRIX control panel OP71 MATRIX Control Panel OP71
64 PR-2009-0021-GB • Subject to modifications • R5-04/2016
Settings economy mode mixing-air damper position
In the “Mixing-air damper position” submenu you can enter in percent the position of
the mixing-air damper that is valid during the economy mode (night operation). This
menu option appears if the “controlled“ function has been configured on the controller.
Settings economy mode outside air volume flow
In the "Outside-air volume flow” submenu you can enter the percentage of outside-air
volume flow that is valid during the economy mode (night operation).
This menu item appears if the function "Controlled outside-air volume flow" was
configured at the controller.
Settings economy mode outside air automatic
In the menu item "OA automatic" you can enter the operation of the mixed-air dampers
which are valid during economy mode (night operation). This menu item appears
whenever the function "Controlled temperature" or "Controlled energy savings" was
configured at the controller .
8.6.16.3 Settings supply air temperature limits
In "supply air limits" submenu you can enter the temperature limits in degrees Celsius
(°C) or Fahrenheit (°F) for:
Heating mode
Cooling mode.
Mixing-air damper position
Value range: 0 ...100 % (for continuous dampers)
Possible intervals: 5 %
Factory setting: 0 %
Variant 0 or 100% (for open/close dampers)
Factory setting: 0%
Outdoor-air volume flow
Value range: 0 ...100 % (for continuous dampers)
Possible intervals: 5 %
Factory setting: 0 %
Recirculating air
Mixed air
Outside air automatic
Value range: Recirculating air, mixed air
Factory setting: Circulating air
NOTICE!
If the function "synchronize setpoints" is activated in the MATRIX control panel OP71
(can be set only using the service tool MATRIX.PC), the menu items room tem-
perature / supply air temperature in submenu "economy mode" are not shown.
Supply-air temperature limits
In heating mode
In cooling mode

Table of Contents