Digital Monitoring Products XR500 Series Installation Guide
28
COMPLIANCE
27.4 Bell
A local audible signal appliance must be used such as Ademco AB12M bell and bell housing.
The alarm housing for a mercantile alarm system without a remote alarm transmission connection shall be mounted
on the outside of the building, visible from a public street or highway. It shall be accessible for examination and
repair. It shall also be located not more than four stories above the street level unless:
a) A second alarm sounding device and housing, intended for outside service, is mounted adjacent to the premises
or area of the building in which the alarm system is installed or
b) A second alarm sounding device, intended for inside service, is mounted within the premises.
In either case, the outside alarm sounding device and housing may be mounted as high as the seventh oor.
27.5 Bell Cuto
The Bell Cuto time cannot be less than 15 minutes.
27.6 Automatic Bell Test
The Automatic Bell Test option must be programmed as YES.
27.7 Standard or Encrypted Line Security
Standard Line Security is provided when congured as a Path 1 NET system using an XR500N panel or an XR500 panel
with an iCOM™ Network Alarm Router. The NET Check-in time must be set to 06 minutes or RND When programmed
for Standard Line Security, Exit Time Restart is disabled. When a dialer is required for 06 minute check-in time, an
attack resistant enclosure (DMP Model 350A) is required. When the check-in time is set to a number less than 200
seconds, an attack resistant enclosure is not required.
To provide Encrypted Line security, install an XR500E panel or an XR500 panel with an iCOM-E™ Encrypted Network
Alarm Router.
For Encrypted Line security operation, communication between the Premise and Supervising Station provides 128 bit
encryption when using an XR500E panel or an XR500 panel with an iCOM-E Encrypted Network Alarm Router.
27.8 Wireless Audible Annunciation Option
The Wireless Audible option must be selected as ANY for commercial applications.
27.9 Model 463C, CELL Only, Standard or Encrypted Line Security
Standard or Encrypted Line Security is provided when programmed using CELL with no backup. XR500 cellular
communication is used as primary with a 3 minute check-in when armed or disarmed.
Path 1 programming
Comm Type: = CELL Checkin: = 3 minute
Path Type: = Primary Fail Time: = 3 minute
Encrypt: = NO or YES* Test Rpt: = NO
Sub Code: = NO or YES
*For Encrypted Line Security, program a Passphrase in Network Options.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DMP Electronics XR500N SERIES and is the answer not in the manual?

DMP Electronics XR500N SERIES Specifications

General IconGeneral
BrandDMP Electronics
ModelXR500N SERIES
CategoryControl Panel
LanguageEnglish

Related product manuals