Digital Monitoring Products XR500 Series Installation Guide
34
COMPLIANCE
31.7 Remote Station Protective Signaling Systems
You must provide 60 hours of standby battery. See section 6.9 in this guide for standby battery calculations. Two
Radionics Model D127 Reversing Relay Modules provide two reversing polarity telephone connections. See the D127
Installation Instruction sheet for wiring details. A DMP Model 893A is used to provide two line dialer communication.
31.8 Fire Protective Signaling Systems using Internet/Intranet/Cell Networks
An Other Transmission Technologies system as dened in UL 864 9th Edition, Section 40.7 may be congured as
NET Primary using a hardwire IP network or CELL Primary using a Model 463C CDMA Cellular Communicator with or
without a backup path. The system may be congured as one of the following:
Path 1 Type NET or CELL Primary with no Backup
Path 1 Programming
Comm Type = NET or CELL Checkin Min = 5
Path Type = Primary Failtime Min = 5
Test Rpt = No Sub Code = Yes
Checkin = Yes Send Comm Trbl = Yes
Path 1 Type NET Primary and Path 2 Type DD Backup
Path 1 Programming Path 2 Programming
Comm Type = NET Comm Type = DD
Path Type = Primary Path Type = Backup
Test Rpt = Yes Test Rpt = Yes
Test Freq = 1 Dy Test Freq = 1 Dy
Send Comm Trbl = Yes Send Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
Path 1 Type NET Primary and Path 2 Type CELL Backup
Path 1 Programming Path 2 Programming
Comm Type = NET Comm Type = CELL
Path Type = Primary Path Type = Backup
Test Rpt = Yes Test Rpt = Yes
Test Freq = 1 Dy Test Freq = 1 Dy
Send Comm Trbl = Yes Send Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
Path 1 Type CELL Primary and Path 2 Type NET Backup
Path 1 Programming Path 2 Programming
Comm Type = CELL Comm Type = NET
Path Type = Primary Path Type = Backup
Test Rpt = Yes Test Rpt = Yes
Test Freq = 1 Dy Test Freq = 1 Dy
Send Comm Trbl = Yes Send Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
31.9 Combination Systems
For combination re and burglary systems, powered burglary devices (PIR, Glassbreak, etc.) must be powered from a
separate listed power supply (DMP Model 505-12). This requirement is not needed for non-powered burglary devices
(door contacts, etc.) which only connect to the zone input of zone expanders or keypads. Refer to Powered Burglary
Devices later in this document.
For combination re and burglary systems, burglary sounding devices such as sirens and bells must be energized
using panel relays, 860 relays, or 716 relays. Programming the output to activate the relay must occur using the
Burglary Bell Output option in Area Information or by the Alarm Action output option of Zone Information. The
Burglary Bell Action option of the panel Bell Options must be programmed as None.
31.10 Remote Annunciators
At least one Model 630F Remote Annunciator must be used on the system. All re alarms, re troubles and
supervisory alarms or troubles must be annunciated only on the 630F. All burglary alarms or troubles must only be
annunciated on non-re keypads. See Status List options of the XR500 Series Programming Guide (LT-0679).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DMP Electronics XR500N SERIES and is the answer not in the manual?

DMP Electronics XR500N SERIES Specifications

General IconGeneral
BrandDMP Electronics
ModelXR500N SERIES
CategoryControl Panel
LanguageEnglish

Related product manuals