XR500 Series Installation Guide Digital Monitoring Products
1
INTRODUCTION
Product Specications Summary
1.1 Power Supply
Transformer Input: Model 327, plug-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16.5 VAC 50 VA
Model 322/323, wire-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16 VAC 56 VA
Model 324/324P, wire-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16 VAC 100 VA
Standby Battery: 12 Vdc, 1.0 Amps Max. charging current
Models 364, 365, 366, 368, or 369
Replace every 3 to 5 years
Auxiliary: 12 Vdc output at 1.5 Amp Max*
12 Vdc output at 325mA used with two Model 364 batteries in the Model 341 enclosure
Bell Output: 12 Vdc at 1.5 Amp Max*
All circuits are inherent Power Limited except the red battery wire and AC terminal.
* For Commercial Burglary and Fire installations, see the Compliance Instructions section. See section 5.3 J12
3-Pin Header for Transformer Types for panel output 2 Amp or 3 Amp current limitations.
1.2 Communication
• Built-in network communication to DMP Model SCS-1R or SCS-VR Receivers (XR500N/XR500E only)
• Built-in encrypted communication to DMP Model SCS-1R Receivers (XR500E only)
• Built-in dialer communication to DMP Model SCS-1R Receivers
• Optional cellular communication to DMP Model SCS-1R or SCS-VR Receivers
• Built-in Contact ID communication to DMP Model SCS-1R Receivers
• Optional 893A Dual Phone Line Module with phone line supervision
• Can operate as a local panel
1.3 Panel Zones
Eight 1k Ohm EOL burglary zones (zones 1 to 8)
Two 3.3k Ohm EOL powered zone with reset (zones 9 and 10)
1.4 Keypad Bus
You can connect up to a total of 16 of the following supervised keypads and expansion modules to the keypad bus:
• Alphanumeric keypads • Four- and/or single-zone expansion modules
• Single-zone detectors • Access control modules
• Wireless Keypads (maximum of 4)
1.5 LX-Bus™
You can connect the following devices to the LX-Bus™ provided on the panel or by the DMP 481, 462N, 462P, 463C
464-263C and 464-263H Interface Cards up to the maximum number of LX-Bus™ addresses. See Accessory Devices in
section 3.4.
• Sixteen-, eight-, four- and/or single-zone expansion modules • Graphic annunciator modules
• Model 521LX or 521LXT Smoke Detectors with CleanMe • Relay output expansion modules
• Model 2W-BLX or 2WT-BLX Smoke Detectors
1.6 Outputs
The XR500 Series provide two Single Pole, Double Throw (SPDT) relay outputs which require the installation of two
Model 305 relays, each rated 1 Amp at 30 Vdc resistive (power limited sources only). A Model 431 Output Harness is
required to use these outputs.
The XR500 Series panels also provide four open collector outputs rated for 50mA each. The open collector outputs
provide ground connection for a positive voltage source. A Model 300 Output Harness is required to use these
outputs.
1.7 Enclosure Specications
The XR500 Series panels are shipped in an enclosure with a transformer, End-of-Line resistors, battery leads, user’s
guide, and programming sheets.
Enclosure
Model
Size Color(s) Construction (Cold Rolled
Steel)
350 17.5”W x 13.5”H x 3.5”D Gray (G) or Red (R) 18-Gauge
350A 17.5”W x 13.5”H x 3.75”D Gray (G) 18-Gauge with 16-Gauge door
341 12.75”W x 6.55”H x 3.15”D Gray (G) 20-Gauge
352X 14.5”W x 32.0”H x 4.0”D Gray (G) 16-Gauge