92
Adr.
Output
Description
Function Code
250
Output value
0000 1111 1111 1111 1111 (16bit
value) LSB is output no.1 MSB is
output no.12
0x03/0x06
251
Output 1 type
0x03/0x06
252
Output 2 type
0x03/0x06
253
Output 3 type
0x03/0x06
254
Output 4 type
0x03/0x06
255
Output 5 type
0x03/0x06
256
Output 6 type
0x03/0x06
257
Output 7 type
0x03/0x06
258
Output 8 type
0x03/0x06
259
Output 9 type
0x03/0x06
260
Output 10 type
0x03/0x06
261
Output 11 type
0x03/0x06
262
Output 12 type
0x03/0x06
Adr.
Others
Description
Function Code
400
Rest position ch1
value <= 4095
401
Rest position ch2
value <= 4095
402
Rest position ch3
value <= 4095
403
Rest position ch4
value <= 4095
404
Volume
value <= 100
0x03/0x06
450
Interface language
0: English 1: French
2: German 3: Spanish
0x03/0x06
990
Parameter value
initialize
Initializations require rebooting.
(It is not initialized to the SD card. If
you want to write to the SD card, you
need to write address 999 after
initialization).
0x06
999
Save setting value
to SD card
If set to a value of 1, the controller is
saved to the SD card.
0x06

Table of Contents