3. WP8010 INSTALLATION
D-306233 CUSDOC PM-10/30 V18 DSC TRIPLE EN INST 41
Configuration Instructions
3. To comply with CP-01 requirements, "00s" and "15s" delays must not be used.
CP-01 features not to be enabled in UL Listed product.
4. To comply with EN requirements, the entry delay must not exceed 45 sec.
This option allows programming the time length of the exit delay. An exit delay allows the user
to arm the system and leave the protected site via specific routes and exit/entry doors without
causing an alarm. Slow-rate warning beeps start sounding once the arming command has been
given, until the last 10 seconds of the delay, during which the beeping rate increases.
Options: 30 seconds; 60 seconds (default); 90 seconds; 120 seconds, 3 minutes and
4 minutes.
1. To comply with UL requirements, do not set to 3 min or 4 min.
2. To comply with CP-01 requirements, the "30s" delay must not be used. CP-01
features not to be enabled in UL Listed product.
The "Exit Delay" time can be further adjusted according to your preferred exit route. The control
panel provides you with the following "Exit Mode" options:
A: "normal" - The exit delay is exactly as defined.
B: “restrt+arm home” - Exit delay restarts when the door is reopened during exit delay. If no
door was opened during exit delay "AWAY", the control panel will be armed "HOME".
C: "restart>reentry" - The exit delay restarts when the door is reopened during exit delay. The
restart occurs once only. Restarting the exit delay is helpful if the user re-enters
immediately after going out to retrieve an item that he left behind.
D: "end by exit" - The exit delay expires (ends) automatically when the exit door is closed
even if the defined exit delay time was not completed.
Options: normal (default); restrt+arm home; restart>reentry and end by exit.
Note: In some WP8010/WP8030 variants, this menu is displayed in the Operation Mode only
(see section 5.14).
Define whether or not the user will be allowed to perform quick arming or not. Once quick
arming is permitted, the control panel does not request a user code before it arms the system.
Options: OFF (default) and ON (default in USA).
Define whether or not the user will be allowed to manually bypass individual zones, or allow
the system to perform automatic bypassing of open zones during the exit delay (i.e.
"force arm"). If a zone is open and "forced arming" is not permitted, the system cannot be
armed and “NOT READY” is displayed. If "no bypass" is selected, neither manual bypassing
nor force arming is allowed which means that all zones must be secured before arming.
Options: no bypass (default); force arm and manual bypass (default in USA).
1. To comply with EN requirements, "manual bypass" must be selected.
2. The option "force arm" is not applicable in the UK.
3. "force arm" or "automatic bypass" feature is not allowed in UL installations; only
"manual bypass" must be enabled. For manual bypass, audible trouble may be
silenced.
4. A zone in Soak Test
1
mode that is configured as bypass will trigger a test fail event
if the system detects a potential alarm event.
5. There is no limit of reported events when a bypass zone is in Soak Test
1
mode.
When "ON", a “latchkey” message will be reported by voice
2
or SMS message to users (see Note)
upon disarming by a “latchkey user” (users 5-8 or keyfob transmitters 5-8 in WP8010system /
users 23-32 or keyfob transmitters 23-32 in WP8030system). This mode is useful when parents at
work want to be informed of a child’s return from school.
Options: OFF (default) and ON.
Notes:
To enable the reporting, you must configure the system to report "alrt" events to Private users
(Latchkey belongs to the "alerts" group of events). Refer to section 5.6.5 "REPORTED
EVENTS" option in both "
VOICE REPORT
" & "
SMS REPORT
" menus.
Latchkey Arming is supplemental in UL installations.
Soak Test is not applicable for UL installations.
Refers to WP8030 with voice option only