6. Function blocks
6.1 Manufacturer function blocks
Other
Retention
The function block does not recognize retentive data.
Sample project configuration
PD=40000 ms; ME=300 ms
Value SV Period duration
PD [ms]
Duty factor
Pulse width
PW [ms]
Off duration
[ms]
0
40000 0 0
5
40000 0 (ME) 40000 (ME)
35
40000 342 39648
1000
40000 9768 30232
1400
40000 13675 27325
2048
40000 20005 19995
3218
40000 31433 8567
3768
40000 36805 3195
4093
40000 40000 (ME) 0 (ME)
1) For devices with transistor outputs
Tab. 85: Effect of various SV values on pulse width for a specific period duration
PW = [SV/4095] ∙ PD
PW = Pulse width (duty factor)
SV = Manipulated variable value
PD = Period duration
372
easyE402/24 MN050009ENEaton.com