 Protection
Contextual help of the web interface – 54
3.5.1.5 Troubleshooting
Card wrong timestamp leads to "Full acquisition has failed" error message on Software
Symptoms:
IPP/IPM shows the error message"The full data acquisition has failed" even if the credentials are correct.
Possible cause:
The Network module timestamp is not correct.
Probably the MQTT certificate is not valid at Network module date.
Action:
Set the right date, time and timezone. If possible, use a NTP server, refer to Contextual
help>>>Settings>>>General>>>System details>>>Time & date settings section.