DL8000 Preset Instruction Manual
E-86 DL8000 Keypad Display Revised February-2016
A. 250 Ohm precision resistor
Figure E-11. AI Modules Field Wiring
Note: Connect a 250 Ω precision resistor (as shown) for the AI-12
module if the AI channel carries a 4–20 mA signal. The AI-16
module has an onboard 250 Ω resistor.
Select AI to perform AI diagnostics:
For traversing use
UP | DOWN
LEFT | RIGHT
ENTER to continue
EXIT to Go Back
EXIT to quit
DO
DI
AO
AI
ACIO
RS232
The system displays a channel selection screen.
Test AI Ch
Use AO Ch
AI ch 1
Specify the AI channel for testing.
Specify (in the Use AO Ch field) the number of the AO channel to
connect to the AI: