135
Reference Manual
00809-0100-4026, Rev KC
Configuration
October 2018
Configuration
5. Select the Level Measurement setup button.
6. Choose the Tank Type which corresponds to the actual tank. If none of the available options matches
the actual tank, choose Unknown.
F
OUNDATION Fieldbus parameter:
TRANSDUCER_1100 > GEOM_TANK_TYPE.
7. Tank Bottom Type is important for the measurement performance close to the tank bottom.
F
OUNDATION Fieldbus parameter:
TRANSDUCER_1100 > GEOM_TANK_BOTTOM_TYPE.
8. Tank Height is the distance from the Upper Reference Point to the tank bottom (see “Tank
geometry” on page 101). Make sure that this number is as accurate as possible.
F
OUNDATION Fieldbus parameter:
TRANSDUCER_1100 > GEOM_TANK_HEIGHT.
9. If the transmitter is mounted in a Still Pipe or Bridle, select the Enable Still Pipe Measurement check
box and enter the Pipe Diameter.
F
OUNDATION Fieldbus parameter:
TRANSDUCER_1100 > SIGN_PROC_CONFIG/Pipe Measurement Enable,
TRANSDUCER_1100 > ANTENNA_PIPE_DIAM.
See “Tank geometry” on page 101 for more information.