136
Reference Manual
00809-0100-4026, Rev KC
Configuration
October 2018
Configuration
10. Select the Environment tab.
11. In the Process Conditions box select the check-boxes that correspond to the conditions in your tank.
You should select as few options as possible and not more than two. See “Process conditions” on
page 103 for more information.
F
OUNDATION Fieldbus parameter:
TRANSDUCER_1100 > ENV_ENVIRONMENT.
Choose the Product Dielectric Constant that corresponds to the current product. If you are
uncertain about the correct range value for this parameter, or if the content in the tank is changing on
a regular basis, choose Unknown.
F
OUNDATION Fieldbus parameter:
TRANSDUCER_1100 > ENV_DIELECTR_CONST.