Safety 
Information
Introduction
Product 
Information
System 
configuration
Mechanical 
Installation
Electrical 
Installation
Getting 
Started
Basic 
parameters
Running 
the motor
Optimization
SMARTCARD 
operation
Onboard 
PLC
Advanced 
parameters
Technical 
Data
Diagnostics
UL Listing 
Information
Unidrive SPM User Guide      121
Issue Number: 3                      www.controltechniques.com
Speed loop gains, below) and to provide torque feed forwards when 
required during acceleration. During the inertia measurement test 
the motor speed changes from 
1
/
3
 to 
2
/
3
 rated speed in the forward 
direction several times. The motor can be loaded with a constant 
torque load and still give an accurate result, however, non-linear 
loads and loads that change with speed will cause measurement 
errors.
To perform an autotune, set Pr 0.40 to 1 for a stationary test, 2 for a 
rotating test, or 3 for an inertia measurement test and provide the drive 
with both an enable signal (on terminal 31) and a run signal (on terminal 
26 or 27).
Following the completion of an autotune test the drive will go into the 
inhibit state. The drive must be placed into a controlled disable condition 
before the drive can be made to run at the required reference. The drive 
can be put in to a controlled disable condition by removing the SAFE 
TORQUE OFF (SECURE DISABLE) signal from terminal 31, setting the 
drive enable parameter Pr 6.15 to OFF (0) or disabling the drive via the 
control word (Pr 6.42 & Pr 6.43).
Setting Pr 0.40 to 4 will cause the drive to calculate the current loop 
gains based on the previously measured values of motor resistance and 
inductance. The drive does apply any voltage to the motor during this 
test. The drive will change Pr 0.40 back to 0 as soon as the calculations 
are complete (approximately 500ms).
For further information refer to section  Pr 0.40 {5.12} Autotune on 
page 139.
Servo
There are five autotune tests available in servo mode, a short low speed 
test, a normal low speed test, an inertia measurement test, a stationary 
test and a minimal movement test. A normal low speed should be done 
where possible as the drive measures the stator resistance and 
inductance of the motor, and from these calculates the current loop 
gains. An inertia measurement test should be performed separately to a 
short low speed or normal low speed autotune.
• A short low speed test will rotate the motor by 2 electrical revolutions 
(i.e. up to 2 mechanical revolutions) in the forward direction, and 
measure the encoder phase angle. The motor must be free from 
load for this test.
• A normal low speed test will rotate the motor by 2 electrical 
revolutions (i.e. up to 2 mechanical revolutions) in the forward 
direction. This test measures the encoder phase angle and updates 
other parameters including the current loop gains. The motor must 
be free from load for this test.
• The inertia measurement test can measure the total inertia of the 
load and the motor. This is used to set the speed loop gains and to 
provide torque feed forwards when required during acceleration. 
During the inertia measurement test the motor speed changes from 
1
/
3
 to 
2
/
3
 rated speed in the forward direction several times. The 
motor can be loaded with a constant torque load and still give an 
accurate result, however, non-linear loads and loads that change 
with speed will cause measurement errors.
• The stationary test only measures the motor resistance and 
inductance, and updates the current loop gain parameters. This test 
does not measure the encoder phase angle so this test needs to be 
done in conjunction with either the short low speed or minimal 
movement tests.
• The minimal movement test will move the motor through a small 
angle to measure the encoder phase angle. This test will operate 
correctly when the load is an inertia, and although a small amount of 
cogging and stiction is acceptable, this test cannot be used for a 
loaded motor.
To perform an autotune, set Pr 0.40 to 1 for a short low speed test, 2 for 
a normal low speed test, 3 for an inertia measurement test, 4 for a 
stationary test or 5 for a minimal movement test, and provide the drive 
with both an enable signal (on terminal 31) and a run signal (on terminal 
26 or 27).
Following the completion of an autotune test the drive will go into the 
inhibit state. The drive must be placed into a controlled disable condition 
before the drive can be made to run at the required reference. The drive 
can be put in to a controlled disable condition by removing the SAFE 
TORQUE OFF (SECURE DISABLE) signal from terminal 31, setting the 
drive enable parameter Pr 6.15 to OFF (0) or disabling the drive via the 
control word (Pr 6.42 & Pr 6.43).
Setting Pr 0.40 to 6 will cause the drive to calculate the current loop 
gains based on the previously measured values of motor resistance and 
inductance. The drive does apply any voltage to the motor during this 
test. The drive will change Pr 0.40 back to 0 as soon as the calculations 
are complete (approximately 500ms).
For further information refer to section  Pr 0.40 {5.12} Autotune on 
page 139.
This parameter defines the required switching frequency. The drive may 
automatically reduce the actual switching frequency (without changing 
this parameter) if the power stage becomes too hot. A thermal model of 
the IGBT junction temperature is used based on the heatsink 
temperature and an instantaneous temperature drop using the drive 
output current and switching frequency. The estimated IGBT junction 
temperature is displayed in Pr 7.34. If the temperature exceeds 145°C 
the switching frequency is reduced if this is possible (i.e >3kHz). 
Reducing the switching frequency reduces the drive losses and the 
junction temperature displayed in Pr 7.34 also reduces. If the load 
condition persists the junction temperature may continue to rise again 
above 145°C and the drive cannot reduce the switching frequency 
further the drive will initiate an ‘O.ht1’ trip. Every second the drive will 
attempt to restore the switching frequency to the level set in Pr 0.41.
The full range of switching frequencies is not available on all ratings of 
Unidrive SP. See section 10.5 Switching frequency on page 147, for the 
maximum available switching frequency for each drive rating.
8.2.7     Motor parameters
Open-loop
This parameter is used in the calculation of motor speed, and in applying 
the correct slip compensation. When auto is selected, the number of 
motor poles is automatically calculated from the rated frequency (Pr 
0.47) and the rated full load rpm (Pr 0.45). The number of poles = 120 * 
rated frequency / rpm rounded to the nearest even number.
Closed-loop vector
This parameter must be set correctly for the vector control algorithms to 
operate correctly. When auto is selected, the number of motor poles is 
automatically calculated from the rated frequency (Pr 0.47) and the rated 
full load rpm (Pr 0.45). The number of poles = 120 * rated frequency / 
rpm rounded to the nearest even number.
Servo
This parameter must be set correctly for the vector control algorithms to 
operate correctly. When auto is selected the number of poles is set to 6.
0.41 {5.18} Maximum switching frequency
RW Txt RA US
OL
Ú
3 (0), 4 (1), 6 (2)
Ö
3 (0)
CL
Ö
VT 3 (0)
SV 6 (2)
0.42 {5.11} No. of motor poles
RW Txt US
OL
Ú
0 to 60 (Auto to 120 Pole)
Ö
Auto (0)
CL
ÚÖ
VT Auto (0)
SV 6 POLE (3)