Proline Prowirl F 200 PROFIBUS PA Electrical connection
Endress+Hauser 43
Hardware addressing
1. Set switch 8 to the "OFF" position.
2. Using switches 1 to 7, set the address as indicated in the table below.
The change of address takes effect after 10 seconds. The device is restarted.
Switch 1 2 3 4 5 6 7
Value in "ON" position 1 2 4 8 16 32 64
Value in "OFF" position 0 0 0 0 0 0 0
2
98
3
4
5 6
7
8
1
DIP
ON
2 + 8 = 10
A0015902
 14 Example of hardware addressing; switch 8 is set to the "OFF" position; switches 1 to 7 define the address.
Software addressing
1. Set switch 8 to "ON".
The device restarts automatically and reports the current address (factory setting:
126).
2. Configure the address via the operating menu: Setup menu→Communication
submenu→Device address parameter
2
98
3
4
5 6
7
8
1
DIP
ON
A0015903
 15 Example of software addressing; switch 8 is set to the "ON" position; the address is defined in the operating
menu ("Setup" menu→"Communication" submenu→"Device address" parameter).
7.5 Ensuring the degree of protection
The measuring device fulfills all the requirements for the IP66/67 degree of protection,
Type 4X enclosure.
To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following
steps after the electrical connection:
1. Check that the housing seals are clean and fitted correctly. Dry, clean or replace the
seals if necessary.
2. Tighten all housing screws and screw covers.
3. Firmly tighten the cable glands.