Commissioning Proline Prowirl F 200 PROFIBUS PA
120 Endress+Hauser
Parameter Prerequisite Description Selection / User
entry
Factory setting
Decimal places 3 A measured value is specified
in the Value 3 display
parameter.
Select the number of decimal
places for the display value.
x
x.x
x.xx
x.xxx
x.xxxx
x.xx
Value 4 display A local display is provided. Select the measured value that
is shown on the local display.
Picklist, see Value 1
display parameter
None
Decimal places 4 A measured value is specified
in the Value 4 display
parameter.
Select the number of decimal
places for the display value.
x
x.x
x.xx
x.xxx
x.xxxx
x.xx
Language A local display is provided. Set display language. English
Deutsch
*
Français
*
Español
*
Italiano
*
Nederlands
*
Portuguesa
*
Polski
*
русский язык
(Russian)
*
Svenska
*
Türkçe
*
中文 (Chinese)
*
日本語
(Japanese)
*
한국어 (Korean)
*
Bahasa Indonesia
*
tiếng Việt
(Vietnamese)
*
čeština (Czech)
*
English
(alternatively, the
ordered language is
preset in the device)
Display interval A local display is provided. Set time measured values are
shown on display if display
alternates between values.
1 to 10 s 5 s
Display damping A local display is provided. Set display reaction time to
fluctuations in the measured
value.
0.0 to 999.9 s 5.0 s
Header A local display is provided. Select header contents on local
display.
Device tag
Free text
Device tag
Header text The Free text option is
selected in the Header
parameter.
Enter display header text. Max. 12 characters
such as letters,
numbers or special
characters (e.g. @,
%, /)
------------
Separator A local display is provided. Select decimal separator for
displaying numerical values.
. (point)
, (comma)
. (point)
Backlight Switch the local display
backlight on and off.
Only for device version
with local display SD03
(touch control)
Disable
Enable
Disable
* Visibility depends on order options or device settings
10.7 Configuration management
After commissioning, you can save the current device configuration, copy it to another
measuring point or restore the previous device configuration.