Proline Prowirl F 200 PROFIBUS PA Commissioning
Endress+Hauser 83
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Format display A local display is provided. Select how measured values
are shown on the display.
• 1 value, max. size
• 1 bargraph + 1
value
• 2 values
• 1 value large + 2
values
• 4 values
1 value, max. size
Value 1 display A local display is provided. Select the measured value that
is shown on the local display.
• Volume flow
• Corrected volume
flow
• Mass flow
• Flow velocity
• Temperature
• Calculated
saturated steam
pressure
*
• Steam quality
*
• Total mass flow
*
• Condensate mass
flow
*
• Energy flow
*
• Heat flow
difference
*
• Reynolds number
*
• Density
*
• Pressure
*
• Specific volume
*
• Degrees of
superheat
*
• Totalizer 1
• Totalizer 2
• Totalizer 3
Volume flow
0% bargraph value 1 A local display is provided. Enter 0% value for bar graph
display.
Signed floating-point
number
Country-specific:
• 0 m³/h
• 0 ft³/h
100% bargraph value 1 A local display is provided. Enter 100% value for bar
graph display.
Signed floating-point
number
Depends on country
and nominal
diameter
Value 2 display A local display is provided. Select the measured value that
is shown on the local display.
Picklist, see Value 1
display parameter
None
Value 3 display A local display is provided. Select the measured value that
is shown on the local display.
Picklist, see Value 1
display parameter
None
0% bargraph value 3 A selection has been made in
the Value 3 display
parameter.
Enter 0% value for bar graph
display.
Signed floating-point
number
Country-specific:
• 0 m³/h
• 0 ft³/h
100% bargraph value 3 An option has been selected in
the Value 3 display
parameter.
Enter 100% value for bar
graph display.
Signed floating-point
number
0
Value 4 display A local display is provided. Select the measured value that
is shown on the local display.
Picklist, see Value 1
display parameter
None
* Visibility depends on order options or device settings
10.5.6 Configuring communication interface
The Communication submenu guides you systematically through all the parameters that
have to be configured for selecting and setting the communication interface.