Commissioning Proline Prowirl F 200 PROFIBUS PA
104 Endress+Hauser
Inlet run
Mating pipe diameter
Installation factor
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Inlet configuration The inlet run correction
feature:
• Is a standard feature and
can only be used in Prowirl F
200.
• Can be used for the
following pressure ratings
and nominal diameters:
DN 15 to 150 (1 to 6")
– EN (DIN)
– ASME B16.5, Sch. 40/80
Select inlet configuration. • Off
• Single elbow
• Double elbow
• Double elbow 3D
• Reduction
Off
Inlet run The inlet run correction
feature:
• Is a standard feature and
can only be used in Prowirl F
200.
• Can be used for the
following pressure ratings
and nominal diameters:
DN 15 to 150 (1 to 6")
– EN (DIN)
– ASME B16.5, Sch. 40/80
Define length of the straight
inlet run.
Dependency
The unit is taken from the
Length unit parameter
0 to 20 m 0 m
Mating pipe diameter – Enter diameter of mating pipe
to enable diameter mismatch
correction.
Detailed information on
diameter mismatch correction:
→ 197
Dependency
The unit is taken from the
Length unit parameter.
0 to 1 m (0 to 3 ft)
Input value = 0:
Diameter mismatch
correction is disabled.
Country-specific:
• 0 m
• 0 ft
Installation factor – Enter factor to adjust for
installation conditions.
Positive floating-
point number
1.0
10.6.4 Configuring the pulse/frequency/switch output
The Pulse/frequency/switch output wizard guides you systematically through all the
parameters that can be set for configuring the selected output type.