Electrical connection Proline Prowirl F 200 PROFIBUS PA
44 Endress+Hauser
4. To ensure that moisture does not enter the cable entry, route the cable so that it
loops down before the cable entry ("water trap").
A0013960
5. Insert dummy plugs into unused cable entries.
7.6 Post-connection check
Are cables or the device undamaged (visual inspection)?
Do the cables comply with the requirements ?
Do the cables have adequate strain relief?
Are all the cable glands installed, firmly tightened and leak-tight? Cable run with "water trap"
→ 43 ?
Depending on the device version: are all the device plugs firmly tightened ?
Does the supply voltage match the specifications on the transmitter nameplate ?
Is the terminal assignment correct ?
Is the terminal assignment or the pin assignment of the device plug correct?
If supply voltage is present, do values appear on the display module?
Are all housing covers installed and firmly tightened?
Is the securing clamp tightened correctly?