Proline Prowirl F 200 PROFIBUS PA Installation
Endress+Hauser 25
Weather protection cover
Observe the following minimum head clearance: 222 mm (8.74 in)
For information on the weather protection cover, see →  181
6.2 Mounting the measuring device
6.2.1 Required tools
For transmitter
For turning the transmitter housing: Open-ended wrench8 mm
For opening the securing clamps: Allen key3 mm
For sensor
For flanges and other process connections: Corresponding mounting tools
6.2.2 Preparing the measuring device
1. Remove all remaining transport packaging.
2. Remove any protective covers or protective caps present from the sensor.
3. Remove stick-on label on the electronics compartment cover.
6.2.3 Mounting the sensor
L
WARNING
Danger due to improper process sealing!
Ensure that the inside diameters of the gaskets are greater than or equal to that of the
process connections and piping.
Ensure that the gaskets are clean and undamaged.
Install the gaskets correctly.
1. Ensure that the direction of the arrow on the sensor matches the flow direction of
the medium.
2. To ensure compliance with device specifications, install the measuring device
between the pipe flanges in a way that it is centered in the measurement section.
3. Install the measuring device or turn the transmitter housing so that the cable entries
do not point upwards.
A0013964