Proline Prowirl F 200 PROFIBUS PA Commissioning
Endress+Hauser 103
Parameter Prerequisite Description Selection / User
entry
Factory setting
Fixed process pressure The following conditions are
met:
• Order code for "Sensor
version", option "Mass flow
(integrated temperature
measurement)"
• In the External value
parameter (→ 102), the
Pressure option is not
selected.
Enter fixed value for process
pressure.
Dependency
The unit is taken from the
Pressure unit parameter
For detailed information
on the calculation of the
measured variables with
steam: → 186
For detailed information
on setting the parameter
in steam applications,
see the Special
Documentation for the
Wet Steam Detection
and Wet Steam
Measurement
→ 212 application
package.
0 to 250 bar abs. 0 bar abs.
Steam quality The following conditions are
met:
• Order code for "Application
package":
– Option ES "Wet steam
detection"
– Option EU "Wet steam
measurement"
• In the Select medium
parameter, the Steam
option is selected.
The software options
currently enabled are
displayed in the
Software option
overview parameter.
Select compensation mode for
steam quality.
For detailed information
on setting the parameter
in steam applications,
see the Special
Documentation for the
Wet Steam Detection
and Wet Steam
Measurement
→ 212 application
package.
• Fixed value
• Calculated value
Fixed value
Steam quality value The following conditions are
met:
• In the Select medium
parameter, the Steam
option is selected.
• In the Steam quality
parameter, the Fixed value
option is selected.
Enter fixed value for steam
quality.
For detailed information
on setting the parameter
in steam applications,
see the Special
Documentation for the
Wet Steam Detection
and Wet Steam
Measurement
→ 212 application
package.
0 to 100 % 100 %
10.6.3 Carrying out a sensor adjustment
The Sensor adjustment submenu contains parameters that pertain to the functionality of
the sensor.
Navigation
"Setup" menu → Advanced setup → Sensor adjustment
‣
Sensor adjustment
Inlet configuration