10 Technical data PROline Promag 53
126 Endress+Hauser
Promag H
Sensor:
• 1/12" - 1" / DN 2 - 25: –4 to +302 °F / –20 to +150 °C (+356 °F/180 °C in prep.)
• 1-1/2" - 4" / DN 40 - 100: –4 to +302 °F (–20 to +150 °C)
Seal:
• EPDM: –4 to +266 °F (–20 to +130 °C)
• Silicone: –4 to +302 °F (–20 to +150 °C)
• Viton: –4 to +302 °F (–20 to +150 °C)
• Kalrez: –4 to +302 °F (–20 to +150 °C)
Conductivity Minimum conductivity:
•≥ 5 µS/cm for fluids generally
•≥ 20 µS/cm for demineralized water
Note that in the case of the remote version, the requisite conductivity is also influenced
by the length of the connecting cable → Page 25.
Limiting medium pressure
range (nominal pressure)
Promag W
• DIN 2501: PN 6 (DN 1200 - 2000), PN 10 (DN 200 - 2000), PN 16 (DN 65 - 2000),
PN 25 (DN 200 - 1000), PN 40 (DN 25 - 150)
• ANSI B16.5: Class 150 (1 - 24"), Class 300 (1 - 6")
• AWWA: Class D (28 - 78")
• JIS B2238: 10K (DN 50 - 300), 20K (DN 25 - 300)
Promag P
• DIN 2501: PN 10 (DN 200 - 600), PN 16 (DN 65 - 600), PN 25 (DN 200 - 600),
PN 40 (DN 15 - 150)
• ANSI B16.5: Class 150 (1/2 - 24"), Class 300 (1/2 - 6")
• JIS B2238: 10K (DN 50 - 300), 20K (DN 15 - 300)
Promag H
The permissible nominal pressure depends on the process connection and seal:
• 580 psig (40 bar): flange, weld nipple (with O-ring seal)
• 230 psig (16 bar): all other process connections