022 Sensor temperature 1.Change main electronic module
2.Change sensor
F Alarm
043 Sensor short circuit 1.Check sensor and cable 2.Change
sensor or cable
S Warning
062 Sensor connection 1.Check sensor connections
2.Contact service
F Alarm
082 Data storage 1. Check module connections
2. Contact service
F Alarm
083 Memory content 1. Restart device
2. Contact service
F Alarm
190 Special event 1 Contact service F Alarm
Diagnostic of electronic
201 Device failure 1. Restart device
2. Contact service
F Alarm
222 Electronic drift Change main electronic module F Alarm
242 Software incompatible 1. Check software
2. Flash or change main electronics
module
F Alarm
252 Modules incompatible 1. Check electronic modules 2.
Change electronic modules
F Alarm
1)
262 Module connection 1. Check module connections
2. Change main electronics
F Alarm
270 Main electronic failure Change main electronic module F Alarm
271 Main electronic failure 1. Restart device
2. Change main electronic module
F Alarm
272 Main electronic failure 1. Restart device
2. Contact service
F Alarm
273 Main electronic failure Change electronic F Alarm
281 Electronic initialization Firmware update active, please
wait!
F Alarm
283 Memory content 1. Reset device 2. Contact service F Alarm
302 Device verification
active
Device verification active, please
wait.
C Warning
1)
311 Electronic failure 1. Reset device 2. Contact service F Alarm
311 Electronic failure 1. Do not reset device
2. Contact service
M Warning
322 Electronic drift 1.Perform verification manually
2.Change electronic
S Warning
382 Data storage 1. Insert DAT module 2. Change
DAT module
F Alarm
383 Memory content 1. Restart device 2. Check or change
DAT module 3. Contact service
F Alarm
390 Special event 2 Contact service F Alarm
Diagnostic of configuration
410 Data transfer 1. Check connection
2. Retry data transfer
F Alarm
411 Up-/download active Up-/download active, please wait C Warning