Proline Promag L 400 PROFIBUS DP Installation
Endress+Hauser 27
Nominal diameter Threaded fasteners Max. screw tightening torque [Nm]
[mm] [mm] Hard rubber Polyurethane PTFE
750 20 × M30 559 – –
800 20 × M30 631 – –
900 24 × M30 627 – –
1 000 24 × M30 634 – –
1 200 32 × M30 727 – –
Screw tightening torques for AS 4087, PN 16
Nominal diameter Threaded fasteners Max. screw tightening torque [Nm]
[mm] [mm] Hard rubber Polyurethane PTFE
350 12 × M24 203 – –
375 12 × M24 137 – –
400 12 × M24 226 – –
450 12 × M24 301 – –
500 16 × M24 271 – –
600 16 × M27 393 – –
700 20 × M27 330 – –
750 20 × M30 529 – –
800 20 × M33 631 – –
900 24 × M33 627 – –
1 000 24 × M33 595 – –
1 200 32 × M33 703 – –
6.2.4 Mounting the transmitter of the remote version
L
CAUTION
Ambient temperature too high!
Danger of electronics overheating and housing deformation.
‣
Do not exceed the permitted maximum ambient temperature (→ 21).
‣
If operating outdoors: Avoid direct sunlight and exposure to weathering, particularly in
warm climatic regions.
L
CAUTION
Excessive force can damage the housing!
‣
Avoid excessive mechanical stress.
The transmitter of the remote version can be mounted in the following ways:
• Wall mounting
• Pipe mounting