Proline Promag L 400 PROFIBUS DP Electrical connection
Endress+Hauser 43
7.3 Special connection instructions
7.3.1 Connection examples
PROFIBUS DP
2
1
A
B
A
B
A
B
3
3
A0021429
 18 Connection example for PROFIBUS DP, non-hazardous area and Zone 2/Div. 2
1 Control system (e.g. PLC)
2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications (→  33)
3 Transmitter
If baud rates > 1.5 MBaud an EMC cable entry must be used and the cable shield must
continue as far as the terminal wherever possible.
7.4 Hardware settings
7.4.1 Setting the device address
PROFIBUS DP
The address must always be configured for a PROFIBUS DP/PA device. The valid address
range is between 1 and 126. In a PROFIBUS DP/PA network, each address can only be
assigned once. If an address is not configured correctly, the device is not recognized by the
master. All measuring devices are delivered from the factory with the device address 126
and with the software addressing method.
Setting the address
1
2
3
4
1
2
3
4
1
2
ON OFF
Not used
Write protection
SW
64
32
16
8
4
2
1
PROFIBUS
address
A0023061
 19 Addressing using DIP switches on the I/O electronics module