Technical data Proline Promag L 400 PROFIBUS DP
126 Endress+Hauser
Protocol-specific data PROFIBUS DP
Manufacturer ID 0x11
Ident number 0x1562
Profile version 3.02
Device description files (GSD,
DTM, DD)
Information and files under:
• www.endress.com
• www.profibus.org
Output values
(from measuring device to
automation system)
Analog input 1 to 4
• Mass flow
• Volume flow
• Flow velocity
• Conductivity
• Electronic temperature
Digital input 1 to 2
• Empty pipe detection
• Low flow cut off
• Verification status
Totalizer 1 to 3
• Mass flow
• Volume flow
Input values
(from automation system to
measuring device)
Analog output 1 (fixed assignment)
External density
Digital output 1 to 2 (fixed assignment)
• Digital output 1: switch positive zero return on/off
• Digital output 2: start verification
Totalizer 1 to 3
• Totalize
• Reset and hold
• Preset and hold
• Stop
• Operating mode configuration:
– Net flow total
– Forward flow total
– Reverse flow total
Supported functions • Identification & Maintenance
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
Configuration of the device
address
• DIP switches on the I/O electronics module
• Via operating tools (e.g. FieldCare)
16.5 Power supply
Terminal assignment (→ 35)
Supply voltage Transmitter
Order code for "Power supply" Terminal voltage Frequency range
Option L
AC100 to 240 V 50/ 60 Hz, ±4 Hz
AC/DC24 V 50/ 60 Hz, ±4 Hz