9 System integration
9.1 Overview of device description files
9.1.1 Current version data for the device
Firmware version 01.00.zz • On the title page of the Operating instructions
• On transmitter nameplate (→ 14)
• Parameter firmware version
Diagnostics → Device info→ Firmware version
Release date of firmware version 05.2014 ---
Manufacturer ID 0x11 Manufacturer ID parameter
Diagnostics → Device info→ Manufacturer ID
Device type ID 0x1562 Device type parameter
Diagnostics → Device info → Device type
Profile version 3.02 ---
9.1.2 Operating tools
The suitable device description file for the individual operating tools is listed in the table
below, along with information on where the file can be acquired.
The suitable device description file for the operating tool is listed in the table below, along
with information on where the file can be acquired.
Operating tool via PROFIBUS
protocol
Sources for obtaining device descriptions
FieldCare • www.endress.com → Download Area
• CD–ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
9.2 Device master file (GSD)
In order to integrate field devices into a bus system, the PROFIBUS system needs a
description of the device parameters, such as output data, input data, data format, data
volume and supported transmission rate.
These data are available in the device master file (GSD) which is provided to the PROFIBUS
Master when the communication system is commissioned. In addition device bit maps,
which appear as icons in the network structure, can also be integrated.
With the Profile 3.0 device master file (GSD) it is possible to exchange field devices made
by different manufacturers without having to reconfigure.
Generally speaking two different GSD versions are possible with Profile 3.0 and higher.
• Before configuring, the user must decide which GSD should be used to operate the
system.
• The setting can be changed via a Class 2 master.
9.2.1 Manufacturer-specific GSD
This GSD guarantees the unrestricted functionality of the measuring device. Device-specific
process parameters and functions are therefore available.
Manufacturer-specific GSD ID number File name
PROFIBUS DP 0x1562 EH3x1562.gsd