Proline Promag L 400 PROFIBUS DP Commissioning
Endress+Hauser 81
10.6.5 Configuring the analog inputs
The Analog inputs submenu guides you systematically to the individual Analog input 1 to
4 submenu. From here you get to the parameters of the individual analog input.
Navigation
"Setup" menu → Analog inputs
‣
Analog inputs
‣
Analog input 1 to 4
Channel
PV filter time
Fail safe type
Fail safe value
Parameter overview with brief description
Parameter Description Selection / User entry Factory setting
Channel Select the process variable. • Volume flow
• Mass flow
• Flow velocity
• Conductivity
• Electronic temperature
Volume flow
PV filter time Specify a time to suppress signal peaks.
During the specified time the totalizer does
not respond to an erratic increase in the
process variable.
Positive floating-point number 0
Fail safe type Select the failure mode. • Fail safe value
• Fallback value
• Off
Off
Fail safe value Specify the value to be output when an error
occurs.
Signed floating-point number 0
10.6.6 Configuring the low flow cut off
The Low flow cut off wizard guides you systematically through all the parameters that
have to be set for configuring the low flow cut off.
Navigation
"Setup" menu → Low flow cut off