Proline Promag L 400 PROFIBUS DP Commissioning
Endress+Hauser 85
Device reset (→ 113)
1) Order code for "Application package", option EC "ECC electrode cleaning"
10.7.1 Carrying out a sensor adjustment
The Sensor adjustment submenu contains parameters that pertain to the functionality of
the sensor.
Navigation
"Setup" menu → Advanced setup → Sensor adjustment
Structure of the submenu
Sensor adjustment
→
Installation direction
Parameter overview with brief description
Parameter Description Selection Factory setting
Installation direction Set sign of flow direction to match the
direction of the arrow on the sensor.
• Flow in arrow direction
• Flow against arrow direction
Flow in arrow direction
10.7.2 Configuring the totalizer
In the "Totalizer 1 to 3" submenu the individual totalizers can be configured.
Navigation
"Setup" menu → Advanced setup → Totalizer 1 to 3
‣
Totalizer 1 to 3
Assign process variable
Unit totalizer
Totalizer operation mode
Failure mode
Parameter overview with brief description
Parameter Description Selection Factory setting
Totalizer operation mode Select totalizer calculation mode. • Net flow total
• Forward flow total
• Reverse flow total
Net flow total
Assign process variable Assignment of a process variable to the
totalizer.
• Volume flow
• Mass flow
Volume flow
Unit totalizer Unit choose list m³