Electrical connection Proline Promag L 400 PROFIBUS DP
34 Endress+Hauser
Connecting cable for remote version
Electrode cable
Standard cable
3 ×0.38 mm
2
(20 AWG) with common, braided copper shield ( ~7 mm (0.28 in)
and individual shielded cores
Cable for empty pipe
detection (EPD)
4 ×0.38 mm
2
(20 AWG) with common, braided copper shield ( ~7 mm (0.28 in)
and individual shielded cores
Conductor resistance ≤50 Ω/km (0.015 Ω/ft)
Capacitance: core/shield ≤420 pF/m (128 pF/ft)
Operating temperature –20 to +80 °C (–68 to +176 °F)
Coil current cable
Standard cable
2 ×0.75 mm
2
(18 AWG) with common, braided copper shield ( ~ 7 mm (0.28"))
and individually shielded cores
Conductor resistance ≤37 Ω/km (0.011 Ω/ft)
Capacitance: core/core,
shield grounded
≤120 pF/m (37 pF/ft)
Operating temperature –20 to +80 °C (–68 to +176 °F)
Test voltage for cable
insulation
≤ AC 1433 V r.m.s. 50/60 Hz or ≥ DC 2026 V
A0003194
8 Cable cross-section
a Electrode cable
b Coil current cable
1 Core
2 Core insulation
3 Core shield
4 Core jacket
5 Core reinforcement
6 Cable shield
7 Outer jacket
Reinforced connecting cables
Reinforced connecting cables with an additional, reinforcing metal braid should be used
for:
• When laying the cable directly in the ground
• Where there is a risk of damage from rodents
Operation in zones of severe electrical interference
The measuring system meets the general safety requirements (→ 145) and EMC
specifications (→ 130).