To decrease the wear on the OTDR connector and
help keep it clean, use an OTDR port protector (30
cm, 12 in) patch cord to connect the OTDR to the
launch and tail cords for bi-directional SmartLoop
tests. These cords are available from Fluke
Networks.
To minimize the effect of the port protector patch
cord on results, do not use a cord longer than
50 cm (20 in).
3 Tap TEST or press .
4 Halfway through the test, the tester tells you to connect the
tail cord to the OTDR port. Make the connections for End 2 as
shown in Figure 186, then tap DONE.
The tester automatically calculates bi-directional averages of loss
measurements. See “Averaged Bi-Directional Results” on
page 478.
WCaution
Switch the launch and tail connections at the end
of the short patch cord. If you switch the
connectors at the patch panel, you will possibly
get less accurate results for those connections
during the second half of the test.
5 If Auto Save is on, the tester uses the next two IDs to save the
results for the two fibers.
If Auto Save is off, and you tap SAVE or FIX LATER, the SAVE
RESULTS screen shows the next two IDs available. You can
change the IDs if necessary.