CHAPTER 2
Core Configuration
Installing the Rack
2-19
FLASHWAVE 7500 Release 6.1
Equipment Installation
Fujitsu and Fujitsu Customer Use Only
FNC-7500-0061-200
Issue 1, May 2009
24 Retighten all mounting hardware.
25 Measure the vertical alignment of the 7-foot equipment rack. It must be vertically aligned to
within 3/16 inch.
26 Is the equipment rack within the tolerance level specified in Step 25 [p. 2-19]?
If YES:
Continue with Step 27 [p. 2-19].
If NO:
Go back to Step 23 [p. 2-18].
27 Update office records according to local procedures.
This procedure is complete.