GE Power Management 269Plus Motor Management Relay 4-
27
4 COMMUNICATIONS FORMAT CODES
4
F16 16 bits Hardware Revision Letter
0000 0000 0000 0000 undefined
0000 0000 0000 0001 A'
0000 0000 0000 0010 B'
etc.
F17 16 bits Product Firmware Revision Code
0000 0001 0000 0000 1.0
0000 0001 0000 0001 1.0.1
0000 0101 0000 0010 5.0.2 (starting B5.0)
0000 0001 0001 0000 1.1.0
etc.
F18 16 bits Modification Number
0000 0000 0000 0000 no modification (i.e. standard unit)
0000 0000 1111 1011 Mod #251
0000 0001 0000 1010 Mod #266
etc.
F19 16 bits Motor Alarm Status 1
0000 0000 0000 0001 Immediate O/L Warning
0000 0000 0000 0010 Ground Fault Alarm
0000 0000 0000 0100 Unbalance Alarm
0000 0000 0000 1000 Undercurrent Alarm
0000 0000 0001 0000 Stator RTD Alarm
0000 0000 0010 0000 Bearing RTD Alarm
0000 0000 0100 0000 Broken Sensor Alarm
0000 0000 1000 0000 Self-Test Failure
0000 0001 0000 0000 Spare Input Alarm
0000 0010 0000 0000 undefined
0000 0100 0000 0000 Power Factor Alarm
0000 1000 0000 0000 Undervoltage Alarm
0001 0000 0000 0000 kvar Limit Alarm
0010 0000 0000 0000 Meter Communication Failure Alarm
0100 0000 0000 0000 Thermal Capacity Alarm
1000 0000 0000 0000 RTD Lotemp Alarm
F20 16 bits Motor Trip Status 1
0000 0000 0000 0001 Overload Trip
0000 0000 0000 0010 Unbalance Trip
0000 0000 0000 0100 Short Circuit Trip
0000 0000 0000 1000 Rapid Trip
Table 4–3: MEMORY MAP FORMAT CODES (Sheet 4 of 7)