Connections and Configuration, continued
D20ME II Jumpering, continued
JP1 -
VME Contr
ol
This jumper sets the Master or Slave function of the board on the VME bus.
Note:
Single-node D20 systems are always set to Master.
JP2 -
VME Address
JP2 is a group of four jumpers that set the VME bus address of the board. The
address should reflect the board location in a D200 CCU chassis.
Example:
The board with address 1 will be the lead node, with nodes 2 through 8
positioned to the right of the lead node.
Note:
Single-node D20s are set to address 0 (all jumpers IN).
JP3-1 and
JP3-2
RTC Options
These two jumpers determine the Real-Time Clock (RTC) source for each D20ME
II board in a CCU:
• Single-node D20s and the first, or lead, node of a D200 both use an internal
clock.
• Non-lead nodes of a D200 synchronize the clocks to the clock of the lead node.
Table: JP4 -
Watchdog
Enable/Disable
This two-position jumper enables or disables the hardware Watchdog.
Note:
Never leave the Watchdog disabled during normal D20ME II operation.
Jumper Position Function
pin 1 to 2
(center)
Disables the hardware Watchdog. JP4
Pin 1 = SLOWCK
Pin 3 = /WD
pin 3 to 2
(center)
Enables the hardware Watchdog.
Table: JP8 –
Battery Backup
Enable/Disable
The D20ME II card has two 3.6V Lithium batteries, Tadiran® TL-2150 or
equivalent, to maintain NVRAM contents in the event of a power failure.
Important:
Disconnect the batteries if you are storing the board for extended periods
of time.
Jumper Position Function
pin 1 to 2 Disconnects the batteries from the NVRAM
pin 3 to 2 Connects the batteries to the NVRAM
JP8
pins 4 to 5 Always jumpered