EasyManua.ls Logo

GE D20 - Procedure: Code Download CCU Base

GE D20
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Energy
D20/D200
Installation and Operations Guide
General 994-0078-2.00-7
Full
105
D20/D200 Software Configuration, continued
Procedure:
Code Download
CCU Base
To download of a flash code file to a CCU type of D20ME module.
Step Action
Code Download for CCU Base type D20ME
1
Restart the D20ME.
2
When messages appear on the monitor, press
SPACEBAR within 5
seconds.
Result:
You are prompted with the message: “Are you sure you wish to
abort the flash boot? (y/n)”
.
3
Type y (or Y) to abort the normal startup.
4
Press
ENTER.
Result:
The login dialog appears.
5
To login: for Login: type westronic and press
ENTER, then for
Password: type rd and press
ENTER.
Result:
After a Welcome message, the D20MES> prompt will appear.
6
Type sp to suspend all processes running on the D20ME
7
Type erase to clear the flash. This will take several seconds.
Result:
The monitor will display, before returning the D20MES>
prompt:
Erasing FLASH memory <
\ Checking FLASH contents… \
Continued on next page

Table of Contents

Other manuals for GE D20