NE-M Installation Guide H5692448
850050111 Issue 03 August 2017 12
Local or remote viewing and configuration of system
parameters, alarm thresholds, and user-definable
alarm inputs and relays
Extensive rectifier/converter Monitoring and Control
Advanced Battery Management to maximize and
manage battery health
Emergency Power Off (EPO) to meet local emergency
services code requirements
System voltage and current monitoring
LVBD and LVLD Low Voltage Disconnect contactor
control and monitoring
dc Distribution monitoring
Standard and Programmable Alarms
Extensive Voltage, Current, Temperature, and Binary
Input monitoring
Standard and programmable Office Alarm relays
Digital communications to all system devices
Remote Peripheral Modules (RPMs)
See the Galaxy Millennium II Installation and User’s Guide for further detail.
Aux Display - NE830A (Optional)
The Aux Display is a voltage monitor that alarms when the voltage of the power system is out of the normal operating
range. It is mounted on the door of the distribution box.
Figure 5 NE830 Display
Fully independent of the main system controller
Displays one or two system voltages and battery state:
Single voltage systems, -48V, +24V
Dual voltage systems, -48V and +24V with common return
The display and LED color indicates battery charge state and wiring errors:
Green display = batteries are not discharging
Red display = batteries are discharging
Amber display = wiring error
A Battery on Discharge alarm relay with form-C contacts is provided
Can be panel, wall or frame rail mounted within 150 ft. of the power system
Rectifiers and Converters
NE-Series rectifiers and converters are hot-pluggable for quick, simple, plug-and-play installation without tools.
Figure 6 Rectifier and Converter Type Badge
NE Eco Rectifiers
Input AC or DC (PV or solar)
Compatibility All Infinity Rectifier Positions
Eco Feature MPPT (Maximum Power Point Tracking) maximizes power harvested from PV arrays
NE Non-Eco Rectifiers
Input AC only
Compatibility All AC powered Infinity Rectifier Positions
5
5
Non Eco rectifiers will not function properly when powered by DC (PV or solar) input in Eco systems.
Type Badge