NE-M Installation Guide H5692448
850050111 Issue 03 August 2017 56
Many systems are shipped with the appropriate controller connections wired by the factory. The following provides a
brief description of how and what to connect to the controller. Use only those sections that apply to the system
configuration.
Step ActionMillennium II
1
Power and Sense Connector
Connect and wire to shunt and alarms.
P6 is a 6-pin connector provided for analog interface to a plant shunt, distribution alarms, and open battery
string alarms. Typically, a factory installed plant wire harness plugs into this connector. This wire set has a
purple wire with a Faston ® receptacle for connecting the Open String Alarm from field installed battery
disconnect breakers.
Table 7 Power and Sense Signals - Millennium II
Pin Wire P6 – Primary Voltage Signal Pin Wire P15 Secondary Voltage Signal
1 BR Return 1 BL Secondary Voltage
2 S 1-Wire Reference 2 BR Return
3 GR
Ground
3 BL/W
Secondary Voltage
4 W/BL
SH2+ (Second Battery Shunt)
4 Y
FAJ (Secondary)
5 W/BR Return 5 - -
6 W/BK
SH1+ (Battery Shunt)
6 BR/W Return
7 O Primary Voltage
8 W FAJ (Primary)
9 O/BK
Primary Voltage
10 BL
SH2- (Second Battery Shunt)
11 W/O Primary Voltage
12 BK
SH1- (Battery Shunt)
2
1-Wire Peripheral Connector
Connect and wire to VT-Probe, external ambient probe, or Remote Voltage Monitor.
P7 is an RJ-45 receptacle for connecting to 1-Wire devices.