EasyManua.ls Logo

GE Infinity M Series - Figure 70 Alarm Relay Jumper Positions - Pulsar Plus; Table 3 Alarm Defaults - Standard Pulsar Plus

GE Infinity M Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NE-M Installation Guide H5692448
850050111 Issue 03 August 2017 49
Step Action Pulsar Plus
3
Configure alarm relays to “Open On Alarm” or “Close On Alarm” as specified in site engineering instructions.
Each Alarm Relay Jumper select “Open On Alarm” or “Closed On Alarm” for one alarm signal and each signal
output can be configured independently.
Carefully move each Alarm Relay Jumper to select “Open On Alarm” or “Close On Alarm” position as per site
engineering instructions with an insulated tool.
Figure 70 Alarm Relay Jumper Positions - Pulsar Plus
The following table contains the alarms along with the factory default alarm assignments to user relays R1-
R7.
Utilize the web interface to change any of the alarm user relay alarm assignments.
Table 3 Alarm Defaults Standard Pulsar Plus
Jumper
Number
Signal
Name
Standard
Defaults
1
PCR
Power Critical Alarm severity indicator
2
PMJ
Power Major Alarm severity indicator
3 PMN Power Minor Alarm severity indicator
4 R1 BD - Battery on Discharge alarm
5 R2 VLV - Very Low Voltage alarm
6
R3
FAJ - External Fuse Major alarm
7
R4
ACF single rectifier input (AC or DC) Fail alarm
8 R5 RFA - single Rectifier Fail alarm
9 R6 MRFA - multiple Rectifier Fail alarm
10 R7 HV - High Voltage shutdown alarm
4
Using optional ES771 Mid-String Voltage Modules?
Yes go to Step 5.
No Go to next section.

Table of Contents

Related product manuals