NE-M Installation Guide H5692448
850050111 Issue 03 August 2017 7
Product Description
Infinity M (NE-M) is available in multiple system arrangements. Block diagram - Figure 1.
Refer to the Infinity M Product Line Brochure for detail description.
Single or Dual Output Voltage
Primary DC Voltage Secondary DC Voltage
(Battery and Rectifiers) (dc/dc Converters)
24V none
24V 48V
48V none
48V 24V
Battery Connections
Direct connection to NE-M system bus
Through a Low Voltage Battery Disconnect (LVBD)
Through battery maintenance switches or circuit breakers located at the battery
DC Distribution
Panel Positions: 2, 3, or 4 (13U, 18U, or 22U systems)
Panels: Bullet Positions, Selectable Bullet Positions, Bolt In Breakers / Fuses
DC Voltage: Primary only or Primary and Secondary
Selectable distribution options
Universal Power Shelf
Accepts rectifiers or converters interchangeably in any power slot
Can be installed with no AC connected, as a converter only shelf
AC Feeds
Front accessible terminal blocks
One or two rectifier positions per feed
Controller
The controller monitors and controls system operation.
Pulsar Plus (Eco features included)
Millennium II
Framework
84 inch, 72inch, or 42 inch frame
Sub-frame - mount in customer provided 23 inch frame
Supplemental Frame
The optional Supplemental Frame and adds DC distribution, power shelves, and battery connections.
Millennium II controller required in Initial Frame.