EasyManua.ls Logo

GE Infinity M Series - Specifications and Application

GE Infinity M Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NE-M Installation Guide H5692448
850050111 Issue 03 August 2017 80
Specifications and Application
Specifications and ordering information are in the Infinity M Product Line Brochure available at
www.gecriticalpower.com
External Surge Protective Device (SPD) is required on all AC inputs.
Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or cabling;
2. can be connected to shielded intra-building cabling grounded at both ends.
Grounding / Bonding NetworkConnect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated
Ground Plane (Mesh-Bonding Network or Common Bonding Network).
Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.
Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).

Table of Contents

Related product manuals