GE Infinity M Series - Troubleshooting - System Alarms; MAJ Fuse Major; MAJ Contactor Open; MIN Battery High Temperature

GE Infinity M Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NE-M Installation Guide H5692448
850050111 Issue 03 August 2017 74
Pulsar Controller Status
Display
Millennium Controller
Status Display
Rect/
Conv
LEDs
Dist.
Module
LED
Possible Problem(s) Possible Solution(s)
MAJ Fuse Major
Norm
green
red
One or more output circuit breakers
or fuses have opened.
1. Clear circuit fault(s).
2. Reset circuit breaker(s) or replace fuse(s).
MAJ Contactor Open
Norm
green
Red
One or more LVD contactors are
manually forced open.
Place disconnect switch(s) in ON position.
MIN Battery High
Temperature
Norm
green
green
Batteries have exceeded
temperature threshold set by user.
1. Check the threshold setting.
2. Call your local field representative.
BD AC DC
-54.48V1 1000A
FLOAT
Display Red
green green red
Minor Distribution
red amber
BD AC DC
-54.48V1 1000A
FLOAT
Display Red
green green red
Minor Battery
red amber
green green green
BD AC DC
-54.48V1 1000A
FLOAT
Display Amber
Minor Battery
amber amber