CHAPTER 9: USING THE D20E MODULE
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL GE INFORMATION 107
Operate a raise/lower DO point
To operate a R/L (raise/lower) Digital Output point:
1. Log in to WESMAINT.
2. Switch to SYSTEM DATA DISPLAYS > DIGITAL OUTPUT DISPLAY.
Result: All DO points appear on the WESMAINT screen.
3. Press the UP or DOWN arrow key (to select the R/L DO point) or press g to enter the
R/L DO point number.
4. Press Ctrl-f.
Result: The password prompt appears at the bottom of the WESMAINT screen.
5. Type in the Password and then press Enter.
6. Press Ctrl-u.
Result: The cursor moves to the command type column.
7. Press the space-bar to move to the Trip/Close command.
8. Type in the ON TIME, OFF TIME and the REPEAT COMMAND number of repeat times.
9. Press Enter again.
Result: The R/L DO point is now active.
10. Repeat this procedure for each required R/L DO point.