64 GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
CHAPTER 3: CONFIGURING THE D20E FIRMWARE
Figure 11: Analog alarm threshold, hysteresis and qualification period
Analog input point quality flag
An Analog Input includes the quality flags listed in Table 13.
Table 13: Analog input quality flags
Analog input configuration settings
Table 14 lists the Analog Input configuration settings and recommended setting values:
Table 14: Analog input point configuration settings
Quality bit Description
On-line Indicates the online or offline state of an analog input point.
Restart Indicates if the device (point) has restarted, but has not been initialized yet.
Communication Lost This bit is set when this point is off-line.
Remote Forced Data This bit is set when the point value is remote forced.
Local Forced Data This bit is set when the point value is locally forced.
Over-range This bit is set when the analog input exceeds the range.
Reference Check This bit is set when the analog input reference is not set (may not be
needed).
Setting Descriptions Range Default
General settings
Reference
Name
Specify a text string that combines the bay name,
group name, and provider name from the General
tab.
Bay Name Specify the name of the bay to which the digital input
belongs.
Group Name Specify a unique name used in conjunction with the
below Point Description setting when referencing the
Provider Application Digital Point information.
The Group Name is used by the HMI for trending and
event querying; therefore, using a label associated
with the substation topology is recommended.
0 to 64 characters
Point Name Specify the name of the point.
The Point Name should be unique within the bay and
group to which it belongs.