50 GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
CHAPTER 3: CONFIGURING THE D20E FIRMWARE
Configure NTP time sync
NOTE
Ensure that the Time Zone of the DAPserver Studio™ and the Time Zone of the Windows
PC are the same before performing the following procedure.
NOTE
NTP server is not to be used as a time source.
NOTE
Only one source of time sync is permitted on the D20E modules.
The Client NTP time sync should be used by the D20E module, and DO NOT use both DNP
and NTP time sync simultaneously.
To time synchronize a D20E module with an NTP time source:
1. Power up the D20E module.
2. Connect the D20E module to DAPserver Studio via the LAN port.
3. Run the DAPserver Studio.
4. Select Time Sync from the Device menu.
Result: The NTP configuration window appears.
5. Type in the IP Address of the D20E module.
6. Type in the Username and Password login credentials.
Result: The Time Sync window appears.