EasyManua.ls Logo

GE PACSystems RX7i - Page 304

GE PACSystems RX7i
469 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 6. Service Request Function
GFK-2950C February 2018 289
Unpacked BCD (2-Digit Year)
In Unpacked BCD format, each digit of the time and date items occupies the low-order four bits of a
byte. The upper four bits of each byte are always zero. This format requires nine words. Values are
hexadecimal.
Parameter Block Format
Address
Example
(Thurs., Dec. 8, 2002, at 9:34:57 a.m.)
1 = change or 0 = read
Address
0h
2 (Unpacked BCD format)
Address+1
2h
High Byte
Low Byte
High Byte
Low Byte
year
Address+2
00h
02h
month
Address+3
01h
02h
day of month
Address+4
02h
08h
hours
Address+5
00h
09h
minutes
Address+6
03h
04h
seconds
Address+7
05h
07h
day of week
Address+8
00h
05h
Unpacked BCD (4-Digit Year)
In Unpacked BCD format, each digit of the time and date items occupies the low-order four bits of a
byte. The upper four bits of each byte are always zero. This format requires nine words. Values are
hexadecimal.
Parameter Block Format
Address
Example
(Thurs., Dec. 8, 2002, at 9:34:57 a.m.)
1 = change or 0 = read
Address
0h
82h (Unpacked 4-digit BCD format)
Address+1
82h
High Byte
Low Byte
High Byte
Low Byte
year
Address+2
00h
02h
month
Address+3
01h
02h
day of month
Address+4
00h
08h
hours
Address+5
00h
09h
minutes
Address+6
03h
04h
seconds
Address+7
05h
07h
day of week
Address+8
00h
05h

Table of Contents