Chapter 6. Service Request Function
GFK-2950C February 2018 319
6.22 SVC_REQ 21: User-Defined Fault Logging
Use SVC_REQ 21 to define a fault that can be displayed in the Controller Fault Table. The fault
contains binary information or an ASCII message. The user-defined fault codes start at 0 hex.
The error code information for the fault must be within the range 0 to 2047 for an Application Msg: to
be displayed. If the error code is in the range 81 to 112 decimal, the CPU sets a fault bit of the same
number in %SA system memory. This allows up to 32 bits to be individually set.
Error Code
Status Bit
Errors 080
No bit set
Errors 81112
Sets %SA
Errors 1132047
No bit set
Errors 204832,767
Reserved
When EN is active, the fault data array referenced by IN is logged as a fault to the Controller Fault
Table. If EN is not enabled, the ok bit is cleared. If the error code is out of range, the ok bit is cleared
and the fault will not be logged as requested.
The parameter block is an input parameter block only with this format:
Parameter address
Error code
MSB
LSB
Address+1
Text2
Text1
Address+2
Text4
Text3
Address+3
Text6
Text5
Address+4
Text8
Text7
Address+5
Text10
Text9
Address+6
Text12
Text11
Address+7
Text14
Text13
Address+8
Text16
Text15
Address+9
Text18
Text17
Address+10
Text20
Text19
Address+11
Text22
Text21
Address+12
Text24
Text23
The input parameter data allows you to select an error code in the range 0 to 2047 and text
information that will be placed in the fault extra data portion of a long controller fault. The controller
fault address, fault group, and fault action are filled in by the function block.